Honeywell AlarmNet GSMBR Installation And Setup Manual page 29

Communications module
Table of Contents

Advertisement

PROMPTS
In Zone Trigger mode, the options for Multi-Mode are "Enabled" or "Disabled." If enabled, whenever a zone on the
communication device is triggered, a corresponding email message is sent INSTEAD of normal central station
reports.
Cover tamper will send email event 8. All communication device system events (such as power loss, low battery, etc.)
are still sent to AlarmNet.
Events used to send email messages are defined on the Honeywell Total Connect web site, and must correspond to
events triggering the hardwired zones.
Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central Station
reporting of critical events (alarms, troubles, etc.).
Multi Mode
10
(Disabled)_
Important Information Regarding Primary Account (Prompts 11-13)
Account information is provided by the central station administrator.
Primary City ID
11
(??)_
Primary CS ID
12
(??)
Primary Sub ID
13
(????)
Device Address
14
(12)_
RemoteAccessY/N
15
(N)_
Direct Wire
Y/N
16
(N)_
Programming for Zone Trigger, 4204 and Two-4204 Modes
4204/
ZONE
ENTRY
2-4204
TRIG.
Important Information Regarding Multi-Mode
OPTIONS
Enable if you want system events sent by email
• Enabled
to the user.
• Disabled
Disable for normal alarm processing.
[01-99]
Enter the 2-digit primary city ID, 01-99
(decimal).
[01-FE]
Enter the 2-digit primary central station ID
number, 01-FE (HEX).
[0001-9999]
Enter the 4-digit subscriber account number,
0001-9999 (decimal).
The module communicates with the control panel
[01-15]
as a 4204 relay module. Enter the appropriate
address. For VISTA-10P, and FA130CP Series
control panels, this must be address 12. For
other controls, see the control panel's
Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to 01-
15. If using 2-4204 mode, the module assigns
the second 4204 to the next higher device
address (e.g., if entering address 12 for the
first 4204, then address 13 is automatically
assigned to the second 4204 module).
Program the control panel accordingly.
2. The device address(es) must be unique from
the "Keypad Address" entered in Prompt 17
and any other address used on the control
panel.
Press [Y] to allow the end user to access their
[Y], [N]
system via a website. Availability of this service
is controlled by the dealer via the web-based
programming tool on the AlarmNet Direct
website.
[Y], [N]
Applies only to control panels that support Direct
Wire.
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 15: "Remote Access" is
disabled, skip to Prompt 18: "Supervision."
Section 3: Programming
DESCRIPTION
3-13