GSMBR / iGSMBR Installation and Setup Guide
PROMPTS
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
34
Enable Zn6 Y/N
(N)_
35
Zn6 Trigger Type
(V+)_
36
Invert Zn6 Y/N
(N)_
37
Restore Zn6 Y/N
(Y)_
38
Delay Zn6 (secs)
(00)_
39
Enable Zn7 Y/N
(N)_
40
Zn7 Trigger Type
(V)_
41
Invert Zn7 Y/N
(N)_
42
Restore Zn7 Y/N
(Y)_
43
Delay Zn7 (secs)
(00)_
Prompts 44 thru 50 appear for the iGSMBR only.
44
Use DHCP Y/N
(Y)_
45
NIC IP Address:
255.255.255.255_
3-8
Programming for ECP Mode
ENTRY
OPTIONS
Important Information Regarding Zone Input Options
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
12 digit:
xxx.xxx.xxx.xxx
DESCRIPTION
Enables alarm reporting for zone 6.
If [N], skip to Prompt 39: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [Space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 44: "Use DHCP."
Selects the triggering method for this zone input.
Press the [Space] key to scroll choices.
Inverts the alarm and normal states of the zone 7
trigger; otherwise, uses normal input signal.
Enables restore reporting for zone 7.
Defines the reporting delay in seconds for zone 7.
Dynamically allocates the IP addresses (recommended);
If [Y], then skip to Prompt 49: "Enable Pwr Save".
If [N], uses fixed IP addresses.
Enter the 4-part address for this device. Each part of
the address must be separated by spaces (displayed as
periods in Review mode).