PW6K1R1E Wiring and Setup

Input Circuit Wiring

2.8 Input Circuit Wiring

Typically, these inputs are used to monitor door position, request to exit, or alarm
contact. Input circuits can be configured as unsupervised or supervised. When
unsupervised, reporting consists of only the open or closed states.
When configured as supervised, the input circuit will report not only open and closed,
but also open circuit, shorted, grounded, and foreign voltage.
Grounded and foreign voltage states are not a requirement of UL 294 and
Note:
therefore not verified by UL.
A supervised input circuit requires two resistors be added to the circuit to facilitate
proper reporting.
The standard supervised circuit requires 1K Ohm, 1% resistors and should be located
as close to the sensor as possible. Custom end of line (EOL) resistances may be
configured via the host software.
The input circuit wiring configurations shown below are supported but may not be
typical:
Figure 2-6: Input Circuit Wiring
IN1
IN2
IN3
IN4

2.9 Relay Circuit Wiring

Two relays are provided for controlling door lock mechanisms or alarm signaling. The
relay contacts are rated at 5A @ 30VAC/DC, dry contact configuration.
Each relay has a Common pole (C), a Normally Open pole (NO) and a Normally
Closed pole (NC).
When you are controlling the delivery of power to the door strike, the
Normally Open and Common poles are used.
10
www.honeywell.com
1K,1%
Standard Supervised Circuit,
Normally Open Contact
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
1K,1%
Unsupervised Circuit,
Normally Closed Contact
Unsupervised Circuit,
Normally Open Contact