Start-Up Procedures; Check Items Before Start-Up - Mitsubishi Electric Q Series User Manual

Motion controller
Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

5 START-UP PROCEDURES

5. START-UP PROCEDURES

5.1 Check Items before Start-up

Part name
(1) Check for looseness, rattling or distorted installation.
(2) Check that the module fixing screw tightening torque is as specified.
(3) Check that the wire sizes of cables are correct.
(4) Check that the power line is wired correctly.
(5) Check that FG is wired correctly.
(6) Check that the FG terminal screws are tightened correctly.
(7) Check that the FG terminal screws are tightening torque is as
(8) Check that the 24VDC wires are twisted as closely as possible and
Q170MCPU
Motion controller
(9) Check that the 24VDC wires are not bind the cable together with
(10) Check that grounding of the earth terminal FG.
(11) Check that the forced stop input is wired correctly.
(12) Check that the battery is installed.
(13) Check that the battery lead connecter is connected correctly.
(14) Check that the internal I/F is wired correctly.
(15) Check that the manual pulse generator/incremental synchronous
(1) Check that the extension base unit is Q52B or Q55B (type not
(2) Check that the model name of module is correct.
(3) Check that the damage for installed modules.
(4) Check that the modules are installed correctly.
(5) Check for looseness, rattling or distorted installation.
(6) Check that the module fixing screw tightening torque is as specified.
Extension base unit
(7) Check that the total I/O points of I/O modules and intelligent function
Q172DLX Servo external
(1).Check that the installation position of modules correspond to the
signals interface module/
Q173DPX Manual pulse
generator interface module
(2) Check that the connection with external equipments is correct.
Table 5.1 Check items before start-up
Confirmation Items
specified.
run in the shortest distance.
and run close to the power wires.
encoder is wired correctly.
requiring power supply module).
modules do not exceed the I/O points of the Motion controller.
system setting.
5 - 1
Check
Reference
4.1.2
4.1.1
4.3.1
4.3.2
4.1.1
4.3.1
4.3
3.2
4.1.4
2.5.1
2.5.2
2.3
4.1.3
4.1.2
4.1.1
Refer to the "Q173DCPU/
Q172DCPU Motion
controller Programming
Manual(COMMON)", or
"QCPU User's Manual
(Hardware Design,
Maintenance and
Inspection).
Refer to the "Q173DCPU/
Q172DCPU Motion
controller Programming
Manual(COMMON).
2.5.3
2.5.4
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q170mcpu

Table of Contents