Error Code List With Operation Via Internal Led - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Error code
Clear text
Fault of compatibility program module to ba-
bAC Er3
sic unit during backup process
Err PrC
Fault of program module
No establishment of flame at the end of safe-
ty time (TSA)
Loc 2
Air pressure faulty (air pressure switch (LP)
welded in no-load position, decrease to spe-
Loc 3
cified time (t10) (air pressure switch (LP) re-
sponse time)
Loc 4
Extraneous light
Air pressure faulty, air pressure switch wel-
Loc 5
ded in working position
Loc 6
Fault of actuator
Loss of flame
Loc 7
Loc 8
---
Loc 9
---
Error not relatable (application), internal error
Loc 10
Loc 12
Valve proving
Loc 13
Valve proving
Loc 14
POC error
Loc 20
Pressure switch min-gas open
Loc 22
Safety loop open
Analog power source 4...20 mA, I <4 mA
Loc 60
Loc 138
Restore process successful
Loc 139
No program module detected
Loc 167
Manual locking
Error in compatibility program module to ba-
rSt Er1
sic unit during restore process
Error in compatibility program module to ba-
rSt Er2
sic unit during restore process
rSt Er3
Error during restore process
Building Technologies
HVAC Products
22 Error code list with operation via in-
ternal LED
Basic Documentation LME7...

22 Error code list with operation via internal LED

Possible cause
Program sequence of program module does not
match to the basic unit
- Error in data content of program module
- No program module fitted
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
Air pressure switch (LP) faulty
- Loss of air pressure signal after specified time
(t10)
- Air pressure switch (LP) is welded in no-load
position
Extraneous light when burner startup
Time out air pressure switch (LP)
- Air pressure switch (LP) is welded in working
position
- Actuator faulty or blocked
- Faulty connection
- Wrong adjustment
Too many losses of flame during operation
(limitation of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
Free
Free
Wiring error or internal error, output contacts,
other faults
Fuel valve 1 (V1) leak
Fuel valve 2 (V2) leak
Error valve closure control POC
Gas shortage
- Pressure switch-max-gas open
- Safety temperature limiter cut out
Wire breakage
Restore process successful
No program module identified
Manual locking
- Program sequence of program module does not
match to the basic unit
- Hardware of basic unit does not match to the
program module
- Program module faulty
- Program module removed during restore
process
116/164