Siemens LME7 Series Basic Documentation page 44

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Parameter
Parameter
number
200
Burner control
224
Specified time (t10) air pressure switch (LP)
225
Gas: Prepurge time (t1)
226
Gas: Preignition time (t3)
230
Interval (t4): End of safety time (TSA) – fuel valve 1
(V1) ON
231
Interval (t9): Fuel valve 1 (V1) ON – pilot valve (PV)
OFF
234
Gas: Postpurge time (t8)
240
Repetition in the event of loss of flame during opera-
tion
0 = None
1 = None
2 = 1 x repetition
247
Continuous pilot (during operation)
0 = Off
1 = On
257
Gas: Postignition time (t3n – 0.3 seconds)
Building Technologies
HVAC Products
Edit
Value range
Min.
Max.
Edit
0 s
13.818 s
Edit
0 s
1237 s
Edit
1.029 s
37.485 s
Edit
3.234 s
74.97 s
Edit
0 s
74.97 s
Edit
0 s
1237 s
Edit
0
2
Edit
0
1
Edit
0 s
13.23 s
Basisdokumentation LME7...
10 PME71.402...
Resolution
Factory setting
Password level
reading from level
0.294 s
13.818 s
SO
4.851 s
29.106 s
SO
0.147 s
3.087 s
SO
0.294 s
3.234 s
SO
0.294 s
2.646 s
SO
4.851 s
19.404 s
SO
1
0
SO
1
0
SO
0.147 s
2.205 s
SO
Password level
writing from level
OEM
OEM
OEM
OEM
OEM
OEM
OEM
OEM
OEM
44/164
CC1P7105de
24.09.2009