Time Table And Settings For Program Sequence Pme72.521 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

11.4 Time table and settings for program sequence PME72.521...

Type
TSA
t1
PME72.521...
tw
max.
min.
Requirement
2.5
3
30
Factory setting
---
---
---
Max.
2.5
3
---
Min.
---
---
30
Step size
---
---
---
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
t3n
Postignition time
1)
Reaction time at change of signal by air pressure switch contact (open of air pressure switch (LP)) and response time in the event of loss of flame
2)
Reaction time at change of signal by inputs (e.g. pressure switch-min (Pmin))
3)
Flame detection time
Building Technologies
HVAC Products
Times in seconds
t3
t3n
t4
t8
t10
min.
approx.
min.
min.
approx.
6
2.5
9
15
15
---
---
---
---
---
---
---
---
---
---
6
---
9
15
---
---
---
---
---
---
Basisdokumentation LME7...
11 PME72.521...
t11
t12
1)
2)
3)
approx.
approx.
300
300
---
---
---
---
---
---
---
---
---
---
1
0.45
0.45
---
---
0.3
0.3
---
---
---
---
---
---
t4
Interval: End of safety time (TSA) – load controller (LR) release
t8
Postpurge time
t10
Specified time air pressure switch (LP) state message (timeout)
t11
Opening time of actuator (timeout)
t12
Closing time of actuator (timeout)
49/164
CC1P7105de
24.09.2009