Building Technologies
HVAC Products
16.2.3 Gas pilot ignition 1 (Gp1/2), 1-stage, with valve proving
Program
SV
Figure 54: Connection diagram fuel train gas pilot ignition 1 (Gp1/2), 1-stage, with valve proving
16.2.4 Gas direct ignition 1 (Gp1/2), 1-stage, with valve proving
Program
SV
Figure 55: Connection diagram fuel train gas direct ignition 1 (Gp1/2), 1-stage, with valve proving
Note:
When valve proving is activated (e.g. on shutdown), the load on the valve's
terminals (according to Technical data / Terminal rating Outputs) is re-
stricted.
Fuel valve 1 (V1) X7-04/4 / (V2) X7-02/3 / auxiliary output AUX
Rated voltage
Rated current
Power factor
If the terminal load (according to Technical data / Terminal rating Outputs) is
not reduced (max. rated current 2 A, cosϕ >0.4), the design life time will be
reached after about 100,000 burner startup cycles!
Basisdokumentation LME7...
16 PME73.840A2
Gas pilot 1, 1-stage
Gp1/2
V1
Gp1/2
AC 120 V
50 / 60 Hz
1 A
cosϕ >0.4
V2
PV
Gas direct 1, 1-stage
V1
V2
AC 230 V
50 / 60 Hz
1 A
cosϕ >0.4
80/164
CC1P7105de
24.09.2009