Time Table And Settings For Program Sequence Pme71.401 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

9.3 Time table and settings for program sequence PME71.401...

Type
TSA
PME71.401...
tw
max.
Requirements
2.5
3
Factory setting
---
t3n+0.45
Max.
2.5
14
Min.
---
---
Step size
---
---
Function parameter
1
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
1)
Reaction time at change of signal by air pressure switch contact (open if air pressure switch (LP)) and response time in the event of loss of flame
2)
Reaction time at change of signal by inputs (e.g. pressure switch-min (Pmin))
3)
Flame detection time
Building Technologies
HVAC Products
Times in seconds
t1
t3
t3n
P225
P226
P257
min.
min.
approx.
30
2
2.5
29.106+2.1
2.058
2.205+0.3
1237+2.1
37.485
13.23+0.3
0+2.1
1.029
0+0.3
4.851
0.147
0.147
Basisdokumentation LME7...
9 PME71.401...
t4
t8
t10
P230
P234
P224
1)
min.
min.
approx.
8
0
15
---
8.232
0
13.818
---
74.97
1237
13.818
1
0.45
3.234
0
0
0.3
0.3
0.294
4.851
0.254
---
Parameter number
Factory setting
P240
0
t3n
Postignition time (P257 +0.3 seconds)
t4
Interval: End of safety time (TSA) – load controller (LR) release
t8
Postpurge time
t10
Specified time air pressure switch (LP) state message (timeout)
2)
3)
---
---
---
---
0.45
---
---
---
35/164
CC1P7105de
24.09.2009