Building Technologies
HVAC Products
Safety loop (SL) X3-04/2, safety valve
(SV) X6-03/3, POC X2-02/3
•
Rated voltage
•
Total current
•
Power factor
4.4 Cable lengths
•
Mains supply line
•
Display, BCI
•
Load controller (LR)
•
Other lines
•
Remote reset (lay separate cable)
•
Fuel valve
Specification as per EN 60730-1
Type of shutdown or interruption of each circuit
Shutdown with micro switch
Mode of operation
4.5 Actuators
Closed / ignition position / open X2-09/1, X2-09/2, X2-09/3
Rated voltage
Rated current
Power factor
Output K2/2 X2-09/7
Rated current
Power factor
Feedback via input of cam V2, depending on the switching contact used in actuator
X2-09/8!
4.6 Cross-sectional areas
The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the
safety loop (safety limit thermostat, water shortage, etc.) must be sized for rated cur-
rents according to the selected external primary fuse.
The cross-sectional areas of the other cables must be sized in accordance with the in-
ternal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must be suited for the respective temperature and environmental con-
ditions!
Basic Documentation LME7...
4 Technical Data
AC 120 V
AC 230 V
50 / 60 Hz
50 / 60 Hz
2 A
2 A
Cosϕ >0.4
Cosϕ >0.4
Max. 100 m (100 pF/m)
For use under the burner hood or in a
control panel
Max. 1 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
Max. 30 m (100 pF/m)
1 pole
Type 2 B
AC 230 V, 50 / 60 Hz
0.1 A (at 1 mio. switching cycles)
Cosϕ >0.6
AC 230 V, 50 / 60 Hz
Max. 1 A
Cosϕ >0.4
0.75 mm²
(single- or multi-core to VDE 0100)
21/164
CC1P7105en
13.10.2009