Manual Adjustment (Depends On Program Module); Position Of Actuator In The Modulating Operation With Analog Signal - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Note
This display is only possible:
A
A
1...3 s
A
>3 s
Building Technologies
HVAC Products
21.4
Manual adjustment (depends on program
module)
21.4.1
Position of actuator in the modulating operation with
analog signal
in operating mode or in standby
when program sequence for modulating operation via analog preset output and with con-
nected actuator with potentiometer for position feedback to the LME7...
Basic Documentation LME7...
21 Operation via internal LED
A
Press
to get in the display for the relative actual posi-
tion of actuator.
The signal lamp flashes green.
The display shows .oP .
Press (1...3 seconds)
tual position.
The signal lamp flashes green.
The relative value .57 of actual position is displayed.
Position of actuator 0°
0 Ω value of potentiometer = 0 % display
Position of actuator high-fire >0°
<90° = value of potentiometer >0 Ω <1000 Ω = 100 % dis-
play
Example: Value .57
When pressing (>3 seconds)
number begins flashing.
When the button is released, the value will be displayed for
2 minutes.
The signal lamp flashes green.
After this time the normal display will be displayed.
Display: Value 57 , point . blinks.
A
button for display the relative ac-
A
button, the point after the
108/164