Siemens LME7 Series Basic Documentation page 95

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Parameter
Parameter
number
500
Ratio control
Actuator position during prepurge time (t1) and postpurge time
515
(t8)
0: Purging in low-fire
1: Purging in high-fire
600
Power setting
654
Analog input (feedback potentiometer ASZxx.3x required)
0 = 3-position step input
1 = 0...10 V
2 = 0...135 Ω
3 = 0...20 mA
4 = 4...20 mA with lockout at I <4 mA
5 = 4...20 mA
700
Error history
701
Current error:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
702
Error history former 1:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
711
Error history former 10:
00: Error code
01: Startup meter reading
02: MMI phase
03: Power value
Building Technologies
HVAC Products
Edit
Value range
Min.
Max.
Edit
0
1
Edit
0
5
Read only
2
255
0
999999
---
---
0 %
100 %
Read only
2
255
0
999999
---
---
0 %
100 %
Read only
2
255
0
999999
---
---
0 %
100 %
Basisdokumentation LME7...
15 PME73.830A2
Resolution
Factory setting
Password level
reading from level
1
1
SO
1
1
SO
---
Service
1
1
---
1
---
Service
1
1
---
1
---
Service
1
1
---
1
Password level
writing from level
OEM
SO
---
---
---
77/164
CC1P7105de
24.09.2009