Siemens LME7 Series Basic Documentation page 91

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

15.4 Time table and settings for program sequence PME73.830...
Type
TSA
PME73.830...
tw
max.
Requirement
2.5
3
Factory setting
---
t3n+0.45
29.106+2.1
Max.
2.5
14
1237+2.1
Min.
---
---
Step size
---
---
Function parameter
1
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Valve proving
2
0: Inactive
1: Active
3
Valve proving
0: During prepurge time (t1)
1: During postpurge time (t8)
4
Valve proving
0: According to P241.01
1: During prepurge time (t1) and postpurge time (t8)
Actuator position during prepurge time (t1) and postpurge time (t8)
5
0: Purging in low-fire
1: Purging in high-fire
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
t3n
Postignition time (P257 +0.3 seconds)
t4
Interval: End of safety time (TSA) - fuel valve 1 (V1) ON
t5
Interval: Pilot valve (PV) OFF - load controller (LR) release
t8
Postpurge time
t9
Interval: Fuel valve 1 (V1) ON - pilot valve (PV) OFF
1)
Reaction time at change of signal by air pressure switch contact (open of air pressure switch (LP)) and response time in the event of loss of flame
2)
Reaction time at change of signal by inputs (e.g. pressure switch-min (Pmin))
3)
Flame detection time
4)
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON), after main ON, with lockout, P234 (postpurge time (t8)) = 0 (postpurging) or P241.01 = 0
5)
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON) and P234 (postpurge time (t8)) >0 (postpurging) and P241.01 = 1
Building Technologies
HVAC Products
t1
t3
t3n
t4
P225
P226
P257
P230
4)
min.
approx.
min.
min.
30
6
2.5
9
6.174
2.205+0.3
9.408
37.485
13.23+0.3
74.97
0+2.1
1.029
0+0.3
3.234
4.851
0.147
0.147
0.294
Parameter number
t10
t11
t12
t22
td1
td2
td3
td4
Basisdokumentation LME7...
15 PME73.830A2
Times in seconds
t8
t5
t9
P234
t10
P232
P231
5)
approx.
min.
approx.
min.
8.5
15
3
15
8.82
19.404
2.646
13.818
74.97
1237
74.97
13.818
2.058
0
0
0
0.294
4.851
0.294
0.294
Factory setting
P240
0
P241.00
1
P241.01
1
P241.02
0
P515.00
1
Specified time air pressure switch (LP) state message (timeout)
Opening time of actuator (timeout)
Closing time of actuator (timeout)
2nd safety time (TSA2)
Test atmospheric pressure
Test gas pressure
Test space filling
Test space evacuating
t11
t12
P259
P260
t22
1)
2)
approx.
approx.
300
300
t9+1
---
---
300.762
300.762
---
---
---
1237
1237
---
1
0.45
0
0
---
0.3
0.3
4.851
4.851
---
---
---
td1
td3
3)
td2
td4
min.
max.
---
10
3
---
10.29
2.646
0.45
37.485
2.646
---
1.029
0
---
0.147
0.147
73/164
CC1P7105de