Structure Of The Display - Siemens RVW26.000B27 Basic Documentation

Electronic air / fuel ratio control system
Table of Contents

Advertisement

44/69
Siemens Building Technologies
HVAC Products

15.1 Structure of the display

6
R
1
Display of «E»
if fault occurred
Current type of fuel
1 Fuel 1
2 Fuel 2
Current program phase
0
Ready for burner start
1
Start of fan and end switch test
2
Actuators open, fan runs up to maximum speed
3
Prepurging
4
Approaching ignition positions
5
Waiting for fuel release
6
Interval
7
Aproaching low-fire (or ignition load)
R
Operating position
8
Postpurging
9
Actuators close
Current programming level
(change with buttons «
0
Normal operation
1
Configuration of system 1
2
Measuring the end switches
3
Configuration of system 2
4
Functions
5
Curve characteristics
6
Ignition positions
F
Data transfer RZD20
X
Fault protocol
RVW26... stores its data in the RZD20
Fig. 24
Display of the handheld terminal AZW20.20
Electronic Air / Fuel Ratio Control System
15 Programming the RVW26...
S e t L o a d
A
u
x
1
P
o s
A
u
x
2
P
o
Parameter name
(select with buttons « D , »
Ü
Þ
,
»)
>
2 5 . 0
:
9
. 5
s
:
8
.
Parameter value
(change with buttons « + -»
If marked with >, # or ^)
Parameter status
Parameter can be set
:
>
Parameter has been selected and
can be changed
=
Parameter cannot be set; display only
#
Parameter has been selected; actuator is
still traveling; parameter can be changed
^
Parameter can be changed without having
an impact on the burner (e.g. to check the
programmed data)
CC1P7873.1en
0
4
5
15.10.2002