APPENDICES
Appendix 1.2 Combinations of A/D converter module functions and GX Configurator-AD
software versions
The following table indicates the A/D converter module functions and corresponding
GX Configurator-AD software versions.
Function
Normal resolution mode
High resolution mode
1
High resolution mode status flag (X8)
2
Maximum value/minimum value reset
completed flag (XD)
1
2
Multiple CPU system compatibility
Normal mode - offset/gain setting mode
switching
3
Appendix 1.3 Precautions for replacing the module of function version A with the one of
function version B or later
(1)
(2)
(3)
App. - 2
SW0D5C-QADU
-E 00A
1
1
1
Functions added by function version B.
2
When the A/D converter module is function version A and the GX Configurator-AD
software version is the SW0D5C-QDAU-E 20C or later or GX Configurator-AD Version
1.10L or later, OFF is always displayed.
3
Functions added by function version C.
Incorporation into an existing system
You can use the wiring designed for function version A as-is to mount the A/D
converter module of function version B or later.
Program utilization
You can use the program created for function version A as-is with the A/D
converter module of function version B or later.
Switch setting for intelligent function module
The setting of the offset/gain setting mode differs between function versions A
and B or later.
Perform the offset/gain settings after checking the RUN LED flashes in
offset/gain setting mode. If the RUN LED does not flash, check to see if the
switch 4 setting is correct.
(Refer to Section 4.5 for the intelligent function module switch setting of function
version B or later.)
<Contents of switch 4 setting for function version A>
H
00
01
00
: Normal mode (A/D conversion processing)
H
01
to FF
: Offset/gain setting mode
H
H
Software version
GX Configurator-
SW0D5C-QADU
AD Version 1.10L
-E 10B
: Compatible
: With temperature drift correction
H
to FF
: Without temperature drift correction
H
H
MELSEC-Q
GX Configurator-
AD Version 1.16S
to 1.15R
or later
: Not compatible