Appendix 2.1 G(P).Offgan - Mitsubishi Electric Melsec Q Series User Manual

Analog-digital converter module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

APPENDICES

Appendix 2.1 G(P).OFFGAN

Internal device
Setting
(System, user)
data
Bit
(S)
[Instruction
[Execution
symbol]
condition]
G.OFFGAN
GP.OFFGAN
Setting
data
Un
Start I/O number of the module
Mode switching
0: Switching to normal mode
(S)
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to
offset/gain setting mode".
App. - 4
Switches the mode of the A/D converter module. (Normal mode to offset/gain setting
mode, offset/gain setting mode to normal mode)
Link direct device
File
register
Word
Bit
Command
Command
Description
(1) Function
Switches the mode of the A/D converter module.
• Normal mode to offset/gain setting mode (Offset/gain setting mode flag (XA)
turns on.)
• Offset/gain setting mode to normal mode (Offset/gain setting mode flag (XA)
turns off.)
POINT
(1) When the offset/gain setting mode is switched to the normal mode, Module
READY (X0) turns from off to on.
Note that initial setting processing will be executed if there is a sequence
program that makes initial setting when Module READY (X0) turns on.
(2) When the offset/gain setting mode is switched to the normal mode, the A/D
converter module holds the previous operation condition and resumes
operation automatically under the previous operation condition.
(2)
Operation error
No errors.
Usable devices
Intelligent
J \
function
module
device
Word
U \G
Setting data
Constant
Index
register
Z
K, H
G.OFFGAN
Un
GP.OFFGAN
Un
Setting range
0 to FE
H
0 ,1
MELSEC-Q
Others
$
(S)
(S)
Data type
Binary 16 bits
Binary 16 bits
App. - 4

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec q64adMelsec q68advMelsec q68adi