7
ONLINE MODULE CHANGE
MELSEC-Q
7.3.4 When user range setting is used and initial setting was made with GX Configurator-AD
(other system is unavailable)
(1) Conversion disable
(a)
On the Operating condition setting screen of GX Configurator-AD, set
"Disable" in the Setting value field of CH
A/D conversion enable/disable
setting, and click the [Execute test] button.
Monitor A/D conversion completed flag (buffer memory address 10:
Un\G10) and confirm that conversion has stopped.
7 - 19
7 - 19