Offset/Gain Setting Operation (Function Version C Or Later) - Mitsubishi Electric Melsec Q Series User Manual

Analog-digital converter module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-AD)

5.6.2 Offset/gain setting operation (Function version C or later)

5 - 21
Perform the offset/gain setting operation in the following sequence.
(1)
Switch to the offset/gain setting screen
Perform the operation in Section 5.6.1 to display the offset/gain setting screen.
At this point, a dialog box to confirm the transition of module's operation mode
(normal mode -> offset/gain setting mode) is displayed. Click the
transit to the offset/gain setting mode.
(2) Specify channels
Place check marks in "Channel selection" column to specify the channels for
each of which the offset or gain setting is to be made.
(3) Apply current/voltage
Apply current or voltage to the module.
(4) Execute offset/gain setting
For each of the channels specified in (2), click the
Gain setting
button to execute respective setting.
(5)
Write settings into the module
Write the content set by operations (2) to (4) into the module by clicking the
Registration button.
(a)
Precautions
Do not perform the following operations during writing the content set by
clicking the
occurs in E
properly.
• Powering off the programmable controller CPU.
• Resetting the programmable controller CPU.
Registration
button into the module. If performed, an error
2
PROM data and the A/D converter module may not operate
MELSEC-Q
Yes button to
Offset setting
or
5 - 21

Advertisement