When User Range Setting Is Used And Initial Setting Was Made With Gx Configurator-Ad (Other System Is Available) - Mitsubishi Electric Melsec Q Series User Manual

Analog-digital converter module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7.3.3 When user range setting is used and initial setting was made with GX Configurator-AD
(other system is available)
7 - 14
(1) Conversion disable
(a)
Take the following steps to disable the conversion:
1)
Set A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) to All channel conversion disable (F
2)
Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3)
Operating condition setting completed flag (X9) turns off from on.
4)
Check that A/D conversion completed flag (buffer memory address 10:
Un\G10) is in a status of Conversion stop (0
5)
Turn Operating condition setting request (Y9) from on to off.
MELSEC-Q
).
H
).
H
7 - 14