14.0

Arming Device Installation

The Door Access Control Module (DACM) is also an
arming device. See Door Access Control Module
(DACM) on page 31 for more information.
14.1

Keypad

14.1.1 Keypad Addressing
Addresses are assigned by setting jumper pins.
Keypads 1 to 8 are assigned to Data Bus Addresses
1 to 8.
Table 3 shows the correct address setting for each
keypad address. See Figure 6 for correct jumper plug
orientation.
Keypad Address Pins
Keypad
1
2
Address
0*
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
OFF
OFF
5
ON
OFF
6
OFF
ON
7
ON
ON
8
OFF
OFF

Table 3: Keypad Address Pin Settings

• Address 0 is reserved for the Installer Keypad. This
keypad is not intended for permanent installation
and should not remain on-premises.
Jumper Plug ON
(covers both pins)

Figure 6: Jumper Plug Configuration

Page 14
P/N: 4998152533-02
PART II: SYSTEM INSTALLATION AND SETUP
4
8
16
MODE
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
Jumper Plug OFF
or
or
Copyright  2007 Bosch Security Systems, Inc.
14.1.1 Keypad Installation
Consult your keypad's installation manual for
complete instructions. Keypads connect to the control
panel in parallel as shown in Figure 7.
You can use either one of the Aux Power (-) terminals
and either one of the 12 VDC (+) terminals when
connecting devices to the control panel.
+12 VDC
Com
Data In
Data Out
Keypad

Figure 7: Keypad to Control Panel Wiring

See Table 4 for control data bus to keypad wire length
requirements.
Control Panel to Keypad
Control Panel to Keypad
using an External Power
Supply

Table 4: Keypad Wire Lengths

If an external power supply is used, follow the lengths
as shown in Table 4.
See Power Outputs on page 8 to determine the total
power output requirements for your system. You
might need to add one or more external power
supplies for the number of keypads you want to use.
Figure 8 shows an external power supply powering a
keypad in a stand-alone configuration.
Figure 8 shows the common from the external power
supply connected to both the keypad's common and
the common on the control panel.
A stand-alone power supply powering any device
connected to the control panel must also be
connected to the Aux – (Aux negative) terminal on the
control panel.
Control Panel
Green
Yellow
Red
Black
BATT+
BATT-
#22 AWG
#18 AWG
(0.8 mm)
(1.2 mm)
1,000 ft.
2,000 ft.
(305 m)
(610 m)
1,000 ft.
2,000 ft.
(305 m)
(610 m)
DS7200V2-UK Installer's Guide

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds7220v2Ds7240v2

Table of Contents