Exit Delay Configuration - Bosch DS7200V2-UK Installer's Manual

Table of Contents

Advertisement

53.0

Exit Delay Configuration

Contact Set/Exit Delay Cancel Zone Options
• Address: 3409
• Default: 1
• Selections: 0-15
Contact Set/Exit Delay Cancel Zone Options
No Contact Set Arming
Enable Contact Set in Area 1
Enable Contact Set in Area 2
Enable Contact Set in Area 3 (DS7240V2 only)
Enable Contact Set in Area 4 (DS7240V2 only)
This parameter selects which areas arm when an Entry/Exit Delay zone restores during Exit Delay and all zones are normal.
Each area can be individually selected to arm on contact (Exit Delay cancel zone).
Contact Set only applies when turning the system All On. If the system is turned Perimeter Only or Partial On, the control
panel only arms at the end of Exit Delay. When any Entry/Exit Delay zone (either Type 1 or Type 2) goes from its alarm (off-
normal) condition to normal, and all other zones in the area are normal or bypassed, Exit Delay is terminated and the control
panel is armed.
If a zone is faulted when the Exit zone restores, the restoral is ignored. Entry/Exit zones might or might not be bypassed. If all
Entry/Exit zones are bypassed and the Exit Delay time is set to 0 (disabled), the control panel cannot be armed All On.
Exit Terminator Zone Options
• Address: 3410
• Default: 0
• Selections: 0-15
Exit Terminator Zone Options
No Terminator Arming
Enable Exit Terminator Arming in Area 1
Enable Exit Terminator Arming in Area 2
Enable Exit Terminator Arming in Area 3 (DS7240V2 only)
Enable Exit Terminator Arming in Area 4 (DS7240V2 only)
This parameter selects which areas arm when an exit terminator button is assigned to that area. Each area can be individually
selected to arm on the activation of an exit terminator button.
Each button only arms the area to which its zone is assigned.
When Exit Delay is active, all zones are normal, and the exit terminator button is pressed, the control panel arms immediately
(see Location ##, Zone Function on page 76 for more information). The exit terminator button applies only to All On arming,
and is assigned a specific zone function. If the control panel is turned Perimeter Only or Partial On, it only arms at the end of
Exit Delay. If a zone is faulted when the button is pressed, the button is ignored.
Page 104
P/N: 4998152533-02
PART IV: CONTROL PANEL PROGRAMMING
0
0
Copyright  2007 Bosch Security Systems, Inc.
Enter This Data Digit to Select Options
1
2
3
4
5
6
7
8
• •
• •
• • • •
• • • • • • • •
Enter This Data Digit to Select Options
1
2
3
4
5
6
7
8
• •
• •
• • • •
• • • • • • • •
9 10 11 12 13 14 15
• •
• •
• • • •
9 10 11 12 13 14 15
• •
• •
• • • •