Rps Direct Connection; Figure 36: Dx4010I/Dx4010 To Control Panel Wiring; Figure 37: Dx4010I/Dx4010 External Power Supply Wiring; Figure 38: Direct Connect Dip Switch Setting - Bosch DS7200V2-UK Installer's Manual

Table of Contents

Advertisement

See Figure 36 and Figure 37 for acceptable power
wiring connections.
You can use either one of the Aux Power (-) terminals
and either one of the 12 VDC (+) terminals when
connecting devices to the control panel.
DX4010i
Black (-)
Green
Yellow
Red (+)

Figure 36: DX4010i/DX4010 to Control Panel Wiring

DX4010i
Black (-)
Green
Yellow
Red (+)
External Power Supply

Figure 37: DX4010i/DX4010 External Power Supply Wiring

Do not tie the black (-) output to earth
ground when using any external power
supply. A ground fault condition is reported
if black (-) is grounded.
Page 26
P/N: 4998152533-02
PART II: SYSTEM INSTALLATION AND SETUP
Control Panel
BATT+
BATT-
Control Panel
BATT+
BATT-
(+)
(-)
12 VDC
Copyright  2007 Bosch Security Systems, Inc.
20.3

RPS Direct Connection

Both modules allow the user to program the control
panel, perform diagnostic functions, and retrieve
history from the control panel in RPS by using a
direct connection between the module and the
control panel.
The control panel's Installer Switch must be
closed in order to perform a remote
programming direct connection.
Follow these steps to connect directly to the control
panel for an RPS session:
1.
Make sure the address DIP switches are set to
Address 0 (zero). See Figure 38 for correct DIP
switch placement. The DX4010 does not use DIP
Switches 7 and 8.
Address 0 (zero) Settings
ON
1
2
3
4
5
6

Figure 38: Direct Connect DIP Switch Setting

2.
Connect the module to Com Port 1 or 2 (or an
available Com Port) on your computer. The
module has a DB9 male serial connector. If this
does not fit your computer, you will need an
adapter.
3.
Connect the module to the control panel:
− DX4010i: Use the supplied RJ-16 to molex
cable to connect the DX4010i to the control
panel. See Figure 39.
Control Panel
AUX/Data
Connector Pin
Location
BATT+
BATT-
DX4010i
RJ-16-to-molex
cable
P3
RJ-16 Data Bus Connector

Figure 39: DX4010i Direct Connection

OFF
7
8
Com Port
Serial Port
LED
ENABLE
Rx Tx
Tx
Rx
BUS
SER
P2
P6
P1
DB9 GND
ENABLE
Null Modem Cable
DS7200V2-UK Installer's Guide
ON

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds7220v2Ds7240v2

Table of Contents