Dx2010 Status Led; Table 11: Dx2010 Address Settings; Table 12: Dx2010 Address Jumper Settings; Figure 22: Dx2010 Dip Switch Configuration - Bosch D6412 Operation And Installation Manual

Hide thumbs Also See for D6412:
Table of Contents

Advertisement

D6412/D4412
Off-Board Sensors Loops
Panel
Location #
D6412/D4412
D6412/D4412
D6412/D4412
D6412 only
D4412 only
For example: You want to use a DX2010 sensor loop for panel Point Location 9 (see Locations in the D6412/D4412 Program
Entry Guide [P/N: 45351] for a detailed description of locations and their relationship to points). You must connect a
DX2010 and set its address DIP switches to 102. Any time the address DIP switches are changed, you must cycle the power to
the module OFF and then ON for the changes to take effect.
Set the address DIP switches as shown in the Table 10. The proper DX2010 DIP switch configuration are shown in Figure 22.
Example:
Module Address 102
8.2.8

DX2010 Status LED

• One flash per second indicates normal operation.
• LED steady ON can indicate any of the following:
-
G wire is not connected or there is a communications problem
between the control panel and the DX2010.
-
No locations (points) are assigned to the DX2010 with this
address. See the Locations section in the D6412/D4412 Program
Entry Guide (P/N: 45351).
-
Address on the DX2010 is not set correctly.
• LED OFF indicates that there is no power to the module.
45349E
For Standard Sensor Loop:
Set Location's Device Parameter to 2.
Set DX2010 Address as shown below.
1 to 8
SDI Address 101
9 to 16
SDI Address 102
17 to 24
SDI Address 103
25 to 32
SDI Address 104
33 to 40
SDI Address 105

Table 11: DX2010 Address Settings

DIP Switches
S1
Module Address
32
101
OFF
102
OFF
103
OFF
104
OFF
105
OFF
106
OFF
107
OFF

Table 12: DX2010 Address Jumper Settings

ON
1
2

Figure 22: DX2010 DIP Switch Configuration

D6412/D4412 Operation and Installation Guide
For Doubled Sensor Loop:
Set Location's Device Parameter to 2.
Set DX2010 Address as shown below.
DIP Switch Settings
S2
S3
S4
16
8
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
3
4
5
6
Page 38
SDI Address 106
SDI Address 106
SDI Address 107
SDI Address 107
S5
S6
2
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
1
2
3
4
5
6

Figure 23: DX2010 Status LED

© 2003 Bosch Security Systems
Status LED

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D4412

Table of Contents