Position Deviation Clear Delay Time; Backlash Compensation Of Feed Step Control - Delta Electronics ASDA-A Series User Manual

Advanced ac servo drive for general purpose applications
Hide thumbs Also See for ASDA-A Series:
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Chapter 7 Servo Parameters|ASDA-A&A+ Series
P2 - 47
PED
Default: 0
Applicable Control Mode: Pr
Unit: 20ms
Range: 0 ~ 250
Settings:
This function is disabled when its setting value is set to 0.
P2 - 48
BLAS
Default: 0
Applicable Control Mode: Pr
Unit: pulse
Range: 0 ~ 10312
Settings:
• A: Pulse Number Settings
0 ~ 312, the pulse number of backlash compensation
Actual pulse number of backlash compensation of motor output shaft is equal to the number
of value A x electronic gear ratio
• B: Polarity Settings
B=0: Forward compensation
B=1: Reverse compensation
1) After modifying the setting value, execute the home sensor function. After executing the
7-66
Call 1(800)985-6929 for Sales

Position Deviation Clear Delay Time

Backlash Compensation of Feed Step Control

A
B
NOTE
home sensor function, perform the control function.
deltaacdrives.com
deltaacdrives.com
sales@deltaacdrives.com
Communication Addr.: 022FH
Related Section:
Section 12.6
Communication Addr.: 0230H
Related Section:
Section 12.6
Revision April 2009
sales@deltaacdrives.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents