Position Deviation Clear Delay Time; Backlash Compensation Of Feed Step Control - Delta Electronics AC Servo Drive ASDA-AB User Manual

Asda-ab series advanced ac servo drive for general purpose applocations
Table of Contents

Advertisement

P2 - 47
PED

Position Deviation Clear Delay Time

Default: 0
Applicable Control Mode: Pr
Unit: 20ms
Range: 0 ~ 250
Settings:
This function is disabled when its setting value is set to 0.
P2 - 48
BLAS

Backlash Compensation of Feed Step Control

Default: 0
Applicable Control Mode: Pr
Unit: pulse
Range: 0 ~ 10312
Settings:
• A: Pulse Number Settings
0 ~ 312, the pulse number of backlash compensation
Actual pulse number of backlash compensation of motor output shaft is equal to the number
of value A x electronic gear ratio
• B: Polarity Settings
B=0: Forward compensation
B=1: Reverse compensation
NOTE
1) After modifying the setting value, execute the home sensor function. After executing the
home sensor function, perform the control function.
Revision January 2009
Chapter 7 Servo Parameters|ASDA-AB Series
A
B
Communication Addr.: 022FH
Related Section:
Section 12.6
Communication Addr.: 0230H
Related Section:
Section 12.6
7-67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents