Installation; Installation Environment; External Dimension; Cabinet Ready In Position - Delta Electronics MVF2000 Series Product Manual

Medium voltage drive
Table of Contents

Advertisement

O
to 70
C, and the relative humidity shall not exceed 95%. The storage environment shall be
out of direct sunlight, corrosion, inflammable gas, conductive dust, salt smog and oil smoke,
etc.
The MVD inside its packaging can be stored in a dry and ventilated place for more than
one year.
If the MVD is unpacked, desiccant shall be put back on when storing it. The wrapped
MVD with VCI gas phase rustproof bag can be put on the wooden pallet and stored for more
than one year in a dry and ventilated place.

6-6 Installation

6-6-1 Installation environment

To ensure the long-term and reliable operation of the MVD, its installation environment shall
meet the following requirements:
The temperature in normal operation environment shall be within 0
ambient temperature exceeds the allowed values, the equipment must be used in
derated operation or equipped with corresponding air conditioning equipment;
The installation altitude shall be lower than 1000m above sea level. When the altitude is
higher than 1000m, the equipment shall be used in derated operation;
The environment relative humidity shall be within 5% to 95% without condensation;
Operation environment: Chemical gas: IEC 721-3-3, class 3C1.

6-6-2 External dimension

The standard appearance and dimension of MVF2000 can be referred to the Annex B.
Electrical parameters and dimensions table.

6-6-3 Cabinet ready in position

For safety and convenience of wiring, it is recommended to install the MVD cabinet on
the cable trench. Installation on top of inflammable objects is prohibited.

6-6-4 Cabinet attachment

After the MVD cabinets are in position and aligned, the cabinets shall be attached each
other.
For In-line cabinet, power cell cabinet with control part and junction part, transformer
cabinets shall be secured to each other. The attachment points between the cabinets are
shown in Fig. 6-10.
Caution!
If the MVD is required to be stored for a longer period, please
contact us.
Solid particle: IEC 721-3-3, class 3S2
Caution!
The installation of the MVF2000 medium voltage drive shall be
conducted under the guidance of professional personnel.
87
o
o