Prepare For Installation - ETC Echoflex Dual Tech Installation Manual

Switch-mount occupancy sensor
Table of Contents

Advertisement

Echoflex Installation Guide
Switch-mount Occupancy Sensor

Prepare for Installation

Dual Tech Switch-mount Occupancy Sensors ship with electronics, a decorator
style wall plate, and a termination kit. The sensor may be installed into an
industry standard back box (provided by others) or surface mounted back box
(sold separately and available from Echoflex).
Compliance
UL/cUL listed, complies with UL508A, UL916, and CSA C22.2 No. 14
CE compliant
For use with Echoflex dimming and relay products.
Environment
Ambient
For indoor, commercial controls use only. Indoor installation only. The sensor
operates in ambient temperatures of -10° C to 40° C, with a maximum of
90% non-condensing humidity.
Installation
Echoflex recommends paying special attention to the installation
environment:
When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.
Do not install the sensor within eight feet from an HVAC airflow
duct/vent.
Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms.
Note:
allow for better vacancy detection results. Reference
DIP Switches on page 5
Dual Tech Switch-mount Occupancy Sensor
In areas of increased noise activity, enabling PIR only mode may
.
Page 2 of 20
Rotary and
Echoflex Solutions, Inc.

Advertisement

Table of Contents
loading

Table of Contents