ETC Echo Dual Tech Ceiling-mount Vacancy Sensor Installation Manual

ETC Echo Dual Tech Ceiling-mount Vacancy Sensor Installation Manual

Advertisement

Quick Links

ETC Installation Guide
Echo Dual Tech Ceiling-mount Vacancy Sensor
Overview
The Echo Dual Tech Ceiling-mount Vacancy Sensor uses passive infrared (PIR)
technology and acoustic detection to provide reliable vacancy sensing for
lighting control. The sensor relies on local station control for manual on and
provides auto off functionality upon detection of vacancy.
The ceiling-mount sensor offers 360 degree coverage with optimized lens
options to accommodate small and large spaces.
Model
Coverage m
E-DVAC-C-SR
41.8 m
Small Room
74.3 m
E-DVAC-C-LR
167 m
Large Room
279 m
Field-installed lens masks are provided to allow customized detection fields
for each sensor lens type.
Custom Configuration
This document guides you through the installation and local DIP switch setup
of the sensor. For more detailed information about custom configuration
options available using EchoAccess, see the EchoAccess App integrated help
system.
Note:
DIP switch 2 must be enabled. See
2
2
 at 2.4 m
2
at 6.7 m
2
at 2.4 m
2
at 6.7 m
To use the configuration settings applied using EchoAccess,
Corpora te He a dqua rte rs Middleton, WI, USA +1 608 831 4116
London, UK +44 (0)20 8896 1000 Holzk irc he n, DE +49 (80 24) 47 00-0
Rome , IT +39 (06) 32 111 683 Hong Kong +852 2799 1220 P a ris, FR +33 1 4243 3535
We
betcconnect.comSupportsupport.etcconnect.com
Conta c
tetcconnect.com/contactETC
Product information and specifications subject to change. ETC intends this document
to be provided in its entirety. Trademark and patent
7 1 8 6 M 2 1 8 4 Rev B Released 2020-12
2
Coverage ft
2
450 ft
 at 8 ft
2
800 ft
at 12 ft
2
1,800 ft
at 8 ft
2
3,000 ft
at 12 ft
DIP Switches on
© 2020 Electronic Theatre Controls, Inc.
page 7.
info: etcconnect.com/ip

Advertisement

Table of Contents
loading

Summary of Contents for ETC Echo Dual Tech Ceiling-mount Vacancy Sensor

  • Page 1 Echo Dual Tech Ceiling-mount Vacancy Sensor Overview The Echo Dual Tech Ceiling-mount Vacancy Sensor uses passive infrared (PIR) technology and acoustic detection to provide reliable vacancy sensing for lighting control. The sensor relies on local station control for manual on and provides auto off functionality upon detection of vacancy.
  • Page 2: Prepare For Installation

    Compliance cULus Listed • CE compliant • For use with ETC Echo Control Systems, powered by an Echo station power supply. Environment Ambient For indoor, commercial controls use only. Operating temperature 0-40°C (32-104°F), humidity maximum 90% (non-condensing). Location...
  • Page 3: Wire Specification

    EchoConnect is a bi-directional protocol that uses one pair of wires (data + and data -) for both data and power. ETC recommends using Belden 8471 Class 2 wire (or approved equal - see the ETC cable cross database etcconnect.com/Support/Cable-Cross-Database for equal alternatives). The total combined length of an EchoConnect wire run using Belden 8471 may not exceed 500 m (1,640 ft), with a maximum distance of 400 m (1,312 ft)
  • Page 4: Installation

    ETC Installation Guide Dual Tech Vacancy Sensor Installation Note: Installation must follow all national and local codes for electrical equipment. NEC Class 2 product to be wired in accordance to NEC Article 725 and local jurisdiction requirements. The ceiling-mount sensor is provided with a mounting plate that can be mounted to a junction box, finished ceiling, or soft ceiling tile.
  • Page 5: Soft Ceiling Tile Installation

    ETC Installation Guide Dual Tech Vacancy Sensor Soft Ceiling Tile Installation Ceiling tile adapter Ceiling tile Ceiling tile adapter 1. Pull the Belden 8471 (or equivalent) and 2.5 mm (14 AWG) ) ground wire to the mounting location and strip each wire 11 mm (7/16 in).
  • Page 6: Set Space And Address

    ETC Installation Guide Dual Tech Vacancy Sensor Settings The Echo Dual Tech Ceiling-mount Vacancy Sensor DIP switches participates in an Echo control system Space and Address using the configured switches Space and Address, which are selectable using the rotary switches on the sensor electronics located behind the removable cover.
  • Page 7: Dip Switches

    ETC Installation Guide Dual Tech Vacancy Sensor DIP Switches DIP switches on the sensor electronics provide for additional configuration options including Use Custom Config, Vacancy Timeout, Enable/Disable detection LEDs, PIR Only Mode, and the ability to restore the sensor to its factory defaults.
  • Page 8: Operation

    ETC Installation Guide Dual Tech Vacancy Sensor Power Up All EchoConnect terminations in the system must be made before applying power to the system and sensor. When the sensor is powered up, the PIR and acoustic detection LEDs illuminate for one minute for calibration and warm- up.
  • Page 9: Vacancy Timeout

    ETC Installation Guide Dual Tech Vacancy Sensor Vacancy Timeout Vacancy timeout is the amount of time the sensor waits to take action after no movement is detected. By default, vacancy timeout is set to 15 minutes (indicated by DIP switch 3 set to Off and 4 set to On; see...
  • Page 10: Lens Masking

    ETC Installation Guide Dual Tech Vacancy Sensor Walk Test The sensor offers a Walk Test mode, which shortens the vacancy timer to ten seconds and allows for simple and quick verification of the sensor’s coverage and range in the installed space.
  • Page 11: Sensor Coverage

    ETC Installation Guide Dual Tech Vacancy Sensor Sensor Coverage Small Room Lens Side View 8 ft 2.4 m 10 ft 3.0 m 12 ft 3.7 m 20 ft 20 ft 15 ft 10 ft 5 ft 5 ft 10 ft 15 ft 6.1 m...
  • Page 12 ETC Installation Guide Dual Tech Vacancy Sensor Dual Tech Vacancy Sensor Page 12 of 12...

This manual is also suitable for:

E-dvac-c-srE-dvac-c-lr

Table of Contents