Echoflex Installation Guide
Switch-mount Occupancy Sensor
Program Zone Start
Note:
zone that will be activated at full with occupancy detection and
deactivated with vacancy detection.
1.
Set the station Function switch to its lowest position of Zone.
2.
Press and hold the [Walk Test / Program Mode] button for three
seconds to enter Program Mode. The "Mode" LED illuminates (steady
amber) and the first button control LED for the station flashes the
current (first) zone controlled.(For example, if the first zone controlled
is Zone 5, the button LED will flash five times.)
3.
Push button 1 to increase the starting zone number by one; any new
count always begins at 1. The station will update the LED indication,
flashing the LED to reflect the new zone number. (For example,
pushing the button control three times will set the first zone for the
station to Zone 3.) All station zone controls will be consecutively
assigned beginning with the specified count.
4.
When the desired zone number is set, press and release the Walk Test
/ Program Mode button to save the new setting. The "Mode" LED
turns off and the button LED will blink the new setting before
returning to normal operation.
Note:
currently set, exit Program Mode then reenter Program Mode; the zone
count will restart at 1.
Dual Tech Switch-mount Occupancy Sensor
The zone that is configured to the button control(s) is also the
To change the assignment to a lower number than what is
Page 14 of 20