Occupancy Sensor

Installation Environment

Paradigm Occupancy Sensors are intended for installation to a finished ceiling
surface, ceiling tile mounted, attached to a round fixture junction box or
single-gang RACO switch box. The sensor operates in ambient temperatures
of -10°C to 40°C, non-condensing humidity.
ETC recommends paying special attention to the installation environment:
• The sensor must have an unobstructed view of the room. Do not mount
behind or near tall cabinets, shelves, hanging light fixtures, etc.
• Do not install the sensor within eight feet from an HVAC airflow duct /
vent.
• Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor view
of these undesired areas. Reference

Parts and Supplies

The following parts and supplies are included with the Unison Paradigm
Occupancy Sensor ordered:
• soft ceiling tile adapter
• LinkConnect & ESD ground
wire pigtails
• 3 each lens masks (spare)
Installation
The Paradigm Occupancy Sensor is provided with a twist-lock mounting plate
that can be mounted to a junction box, finished ceiling or soft ceiling tile.
Determine the installation method and follow the detailed instructions:
See "Junction Box Installation" on page 3.
See "Soft Ceiling Tile Installation" on page 4.
Note:
Occupancy Sensor Installation Guide
The LinkConnect pigtail and WAGO connectors (provided) are
only required when the sensor is installed in series with other
stations or sensors. If you are not continuing the data run, direct
termination on the control board is recommended.
Page 2 of 8
Lens Masking
• 3 position WAGO connectors
• 2 each screws, 6-32 x 3/4" and
1 3/4"