Echoflex Installation Guide
Switch-mount Occupancy Sensor
DIP Switch Settings
DIP switches provide for designation of "Off" functionality, the ability to
disable amber button LEDs, and the ability to restore the sensor to its factory
defaults.
Switch #
1-button Dual Tech Switch-mount Occupancy Sensor only
When set to On, and the function switch is set to Preset, enables
•
Sequence toggle mode. Default position is Off.
2 button Dual Tech Switch-mount Occupancy Sensor only
1
When set to On (default), and the function switch is set to Preset, the
•
bottom button provides a Space Off command.
When set to Off, the bottom button controls the next consecutive preset
•
after the preset assigned to the top button.
Amber LED Disable - provides the ability to disable use of the amber
button LEDs.
When set to On, the amber button LEDs on the station will be disabled.
•
Only blue LEDs will illuminate.
2
When set to Off (default), the amber button LEDs on the station are
•
enabled. Amber LEDs are provided as the default so the station glows in
darkened spaces, allowing it to be easily located.
Vacancy Timeout
5 min = Switches 3 and 4 are Off
•
15 min = Switch 3 is Off and Switch 4 is On (default)
3 and 4
•
30 = Switch 3 is On and Switch 4 is Off
•
Auto = Both switches are On
•
Detection LEDs
When set to On (default), the occupancy detection LED illuminates when
•
movement is detected.
5
When set to Off, the occupancy detection LED is disabled unless the unit
•
is in Walk Test mode.
PIR Only Mode
When set to On, acoustic detection technology is disabled for the
•
sensor.
6
When set to Off (default), both PIR and acoustic detection technologies
•
are used by the sensor.
7
unused
Restore to Defaults at boot
When set to On, then cycling power to the switch-mount station, the
•
8
unit restores to its factory default settings.
Off is the default setting
•
Dual Tech Switch-mount Occupancy Sensor
Use
Page 6 of 20
Echoflex Solutions, Inc.