ETC Echoflex Dual Tech Installation Manual page 10

Switch-mount occupancy sensor
Table of Contents

Advertisement

Echoflex Installation Guide
Switch-mount Occupancy Sensor
PIR (only) Detection
When acoustic detection is disabled (DIP switch 6 set to On), the following
logic is used:
When the space is vacant, PIR detection and manual control can switch
the state to occupied.
When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to ten
seconds and allows for simple and quick verification of the sensor's coverage
and range in the installed space.
1.
Prepare the site for configuration.
2.
Remove the sensor wall plate to gain
access to the [Walk Test] button.
3.
Press the [Walk Test] button on the top right of the sensor to enable
the Walk Test feature at the sensor. A green LED will begin to flash,
indicating Walk Test is enabled and the vacancy timer will be
shortened to ten seconds.
4.
Move throughout the space including corners and areas that may
specifically be obscured from line of sight to the sensor. Each time the
sensor detects movement, the lens will illuminate red. If acoustic
detection is enabled, any sound detected will illuminate the lens
green.
5.
Walk Test mode will automatically exit and return to normal operation
after five minutes. You can also manually terminate by pressing the
[Walk Test] button again.
Dual Tech Switch-mount Occupancy Sensor
a.
Make certain the sensor and lighting
loads are powered and connected
for control by the Elaho control
system.
b.
You will need direct access to the
sensor in order to place it into Walk
Test mode.
Page 10 of 20
Walk Test
Echoflex Solutions, Inc.

Advertisement

Table of Contents
loading