WIRINGS CONNECTION

Compared with HGM7120N, HGM7110N is missing one mains voltage three-phase input terminal.
HGM7120N controller back panel is as follows:
No.
Function
1
B-
2
B+
3
Emergency Stop
4
Fuel (16A)
5
Crank (16A)
6
Aux. Output 1(7A)
7
Aux. Output 2(8A 250VAC)
8
HGM7100N Genset Controller
HGM7100N GENSET CONTROLLER USER MANUAL
Fig. 3 - HGM7120N Back Panel
Table 9 - Terminal Wiring Connection
Cable Size
2
2.5mm
Connected with negative of starter battery
Connected with positive of starter battery. If wire length
2
2.5mm
is over 30m, better to double wires in parallel. Max. 20A
fuse is recommended.
2
2.5mm
Connect emergency stop button with B+.
2
1.5mm
B+ is supplied by No.3 terminal, rated 16A.
B+ is supplied by No.3 terminal, rated 16A.
2
1.5mm
Connect with starting coil of starter.
2
1.5mm
B+ is supplied by No.2 terminal, rated 7A.
Normally
2
rated 8A.
1.5 mm
Relay common port
2020-09-10
Remarks
close
output,
Details see Table 11
Version1.2
Page 18 of 47