Smartgen HGM7100N Series User Manual page 26

Genset controller
Hide thumbs Also See for HGM7100N Series:
Table of Contents

Advertisement

Items
No.
High Temp Warning
4
Setting
Low Temp Warning
5
Setting
Oil Pressure Sensor
1
Curve Type
2
Open Circuit Action
Low Oil Pressure
3
Shutdown Setting
Low Oil Pressure
4
Warning Setting
5
Sensor Type
Level Sensor
1
Curve Type
2
Open Circuit Action
3
Low Level Warning
Low
Level
4
Shutdown
Flexible Sensor 1
Flexible Sensor 1
1
Setting
2
Sensor Type
Flexible Sensor 2
Flexible Sensor 2
1
Setting
Digital Inputs
Digital Input 1
HGM7100N Genset Controller
HGM7100N GENSET CONTROLLER USER MANUAL
Range
Default
(0-300)º C
95
(0-1)
0
(0-15)
7
(0-2)
0
(0-1000)kPa
103
(0-1000)kPa
124
(0-2)
0
(0-15)
4
(0-2)
0
(0-300)%
10
(0-300)%
8
(0-3)
0
(0-2)
0
(0-3)
0
2020-09-10
Description
When
temperature
connected temperature sensor is higher than
the setting point, controller will initiate high
temperature warning alarm (judgment only
starts after safety on delay expired). Return
value and delay value can be set.
0: Disabled; 1: Enabled
SGX. For details see table 13.
0: Warning; 1: Shutdown; 2: None
When pressure value of externally connected
oil pressure sensor is lower than the setting
point, controller will initiate low oil pressure
shutdown alarm (judgment only starts after
safety on delay expired). Delay value can be
set.
When pressure value of externally connected
oil pressure sensor is lower than the setting
point, controller will initiate low oil pressure
warning alarm (judgment only starts after
safety on delay expired). Return value and
delay value can be set.
0: Resistor type; 1: Current type; 2: Voltage
type.
SGH. For details see table 13.
0: Warning; 1: Shutdown; 2: None
When the value of external connected fuel
level sensor is lower than the setting point,
controller will initiate low liquid level warning
alarm (always judge). Return value and delay
value can be set.
When the value of external connected level
sensor is lower than the setting point,
controller will initiate low liquid level shutdown
alarm (always judge). Delay value can be set.
0:
Not
Used;
1:Temperature
2:Pressure Sensor; 3:Fuel Level Sensor
0: Resistor type; 1: Current type; 2: Voltage
type.
0:
Not
Used;
1:Temperature
2:Pressure Sensor; 3:Fuel Level Sensor
Version1.2
value
of
externally
Sensor;
Sensor;
Page 26 of 47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm7110nHgm7120n