Smartgen HGM7100N Series User Manual page 20

Genset controller
Hide thumbs Also See for HGM7100N Series:
Table of Contents

Advertisement

No.
Function
Gen
W-phase
38
Monitoring Input
39
Gen N2-line Input
Mains
R-phase
40
Monitoring Input
Mains
S-phase
41
monitoring input
Mains
T-phase
42
monitoring input
43
Mains line N1 Input
RS485 Common Ground
44
45
RS485-
46
RS485+
VOUT(+5V)
47
NOTE: USB ports in controller rear panel are programmable parameter ports, user can directly configure the
controller via PC.
NOTE: ETHERNET port in controller rear panel is network monitoring port, user can directly monitor the controller
via PC.
HGM7100N Genset Controller
Cable Size
Voltage
Connected to W-phase output of genset (2A fuse
2
1.0mm
recommended).
2
1.0mm
Connected to N-line output of genset.
Voltage
Connected to R-phase of mains (2A fuse recommended).
2
1.0mm
(HGM7110N without)
voltage
Connected to S-phase of mains (2A fuse recommended).
2
1.0mm
(HGM7110N without)
voltage
Connected to T-phase of mains (2A fuse recommended).
2
1.0mm
(HGM7110N without)
2
1.0mm
Connected to N-line of mains. (HGM7110N without)
2
0.5mm
120Ω shielded wire is recommended with single end
2
0.5mm
ground.
2
0.5mm
2
0.5mm
Output DC +5V.
2020-09-10
HGM7100N GENSET CONTROLLER USER MANUAL
Version1.2
Remarks
Page 20 of 47