Smartgen HGM7100N Series User Manual page 23

Genset controller
Hide thumbs Also See for HGM7100N Series:
Table of Contents

Advertisement

Items
No.
14
Charge Alt Fail
15
Start Attempts
Crank
Disconnect
16
Condition
Frequency of Crank
17
Disconnect
Speed
of
Crank
18
Disconnect
Oil
Pressure
19
Crank Disconnect
Battery Low Voltage
20
Start Enabled
Battery Low Voltage
21
Start Value
Battery Low Voltage
22
Stop Value
Battery Low Voltage
23
Start/Stop Delay
Generator
Power
Supply
1
System
2
Engine Poles
3
Rated Voltage
HGM7100N Genset Controller
Range
(0-60.0)V
(1-10)times
(0-6)
(0-200)%
(0-200)%
of
(0-1000)kPa
(0-1)
(1.0-60.0)V
(1.0-60.0)V
(0-3600)s
(0-3)
(2-64)
(30-30000)V
2020-09-10
HGM7100N GENSET CONTROLLER USER MANUAL
Default
If the voltage of charger D+(WL) is lower than
the set value during gen-set normal running,
8.0
controller will initiate fail to charge warning
alarms.
Maximum crank times when engine starts fail.
3
If reach this number, controller will send start
failure signals.
For details please see table 14
There are 3 cranking disconnect conditions,
2
which can be used separately or together,
aiming to disconnect starter motor with
engine as soon as possible.
The set value is the percentage of Gen rated
frequency, when generator frequency is
24
higher than the set value, starter will be
disconnected. For Details please see the
following installation description.
The set value is the percentage of the rated
speed, when speed is higher than the set
24
value, starter will disconnect. For details see
the following installation description.
When engine oil pressure is higher than the
200
set value, starter will disconnect. For details
see the following installation description.
0
0: Disabled; 1:Enabled
It is the low-battery-start value. Active at auto
10.0
mode.
The shutdown value after low-battery-start
24.0
and charged. Active at auto mode.
When battery voltage reached to engine start
threshold, engine will start up after delay
60
expired; when battery voltage reached to
engine stop threshold, engine will stop after
delay expired.
0: 3P4W;
1: 3P3W
0
2: 2P3W
3: 1P2W
It is the number of engine poles, which can be
4
used for engine speed calculation when
speed sensor is not installed.
Provide standards for judging Gen over/under
230
voltage and loading voltage; if PT is used, this
value is primary voltage of PT.
Description
Version1.2
Page 23 of 47