Smartgen HGM7100N Series User Manual page 24

Genset controller
Hide thumbs Also See for HGM7100N Series:
Table of Contents

Advertisement

Items
No.
4
Voltage On-load
5
Rated Frequency
6
Frequency On-load
Voltage
7
Transformer (PT)
Gen. Over Voltage
8
Shutdown
Gen. Under Voltage
9
Shutdown
Gen.
Over
10
Frequency
Shutdown
Gen.
Under
11
Frequency
Shutdown
Gen. Over Voltage
12
Warning
Gen. Under Voltage
13
Warning
Gen.
Over
14
Frequency Warning
Gen.
Under
15
Frequency Warning
Gen. Loss of Phase
16
Check
Gen.
Reverse
17
Phase Check
Load
Current
1
Transformer Ratio
2
Rated Current
3
Rated Power
Over
Current
4
Enable
5
Over Power Setting
HGM7100N Genset Controller
HGM7100N GENSET CONTROLLER USER MANUAL
Range
Default
(0-200)%
85
(10.0-600.0) Hz
50.0
(0-200)%
85
(0-1)
0
(0-200)%
120
(0-200)%
80
(0-200)%
114
(0-200)%
80
(0-200)%
110
(0-200)%
84
(0-200)%
110
(0-200)%
84
(0-1)
1
(0-1)
1
(5-6000)/5
500
(5-6000)A
500
(0-6000)kW
276
(0-200)%
120
(0-1)
0
2020-09-10
Description
The set value is rated voltage percentage.
Controller detects at preparing to take load,
when Gen voltage is less than load voltage, it
won't enter normal running period.
Provide standards for judging over/under
frequency and on-load frequency.
The set value is Gen rated frequency
percentage. The controller detects it while
gen-set prepares to take the load, if
frequency is less than the on-load frequency,
gen-set will not enter normal operation
period.
0: Disabled; 1: Enabled
The set values are rated voltage percentage
of generator, and delay value can be set.
The
set
values
are
percentage of generator, and delay value can
be set.
The set values are rated voltage percentage
of generator, and return value and delay
value can be set.
The
set
values
are
percentage of generator, and return value and
delay value can be set.
0: Disabled; 1:Enabled
It is the ratio of externally connected current
transformer.
It is the rated current of generator, which is
used as the standard for load current.
It is the rated power of generator, which is
used as the standard for load current.
The set value is the percentage of rated
full-load current, and delay value can be set
as DMT or IDMT.
0: Disabled; 1: Enabled
Version1.2
rated
frequency
rated
frequency
Page 24 of 47