X609 Terminal Strip - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.7 Active Interface Modules Chassis-2
4.7.3.6

X609 terminal strip

Table 4- 35
X609 terminal strip
Connector
Terminal
PE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
PE
Max. connectable cross-section: 2.5 mm
NOTICE
Damage to the device as there is no isolating transformer for the fan power supply at
terminal X609:5 ... 8
If an appropriate isolating transformer is not connected upstream of the fan power supply,
then this can cause significant damage to the device.
• When using an external 230 V AC supply for the fan, carefully ensure that the following
Note
Cable gland and cable holder
Under terminal X609, there is a cable gland in the front cover and cable holders for securing
the cables.
110
Designation
PE
P24
P24
M
M
L
L
N
N
Control of fan con-
tactor
Control of fan con-
tactor
NC
NC
NC
NC
PE
2
conditions are complied with:
– Use an isolating transformer whose secondary is grounded on one side.
– The harmonic load must be less or equal to what is stipulated in EN 61000-2-4.
– The line quality must be in compliance with EN 61000-4-11 and EN 61000-2-4.
Technical specifications
PE connection
External 24 V DC supply
Voltage: 24 VDC (20.4 ... 28.5 V)
Current consumption: Max. 0.25 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 4 A
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
PE connection
to Active Line Module
Chassis-2, X9:HS1
to Active Line Module
Chassis-2, X9:HS2
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3