DC link components
7.1 Braking Module
Note
"Overvoltage" fault
Even when the response threshold is set to a low value, the DC-link voltage can still reach the
maximum voltage value (hardware shutdown threshold), thus triggering the "Overvoltage"
fault. This can occur, for example, in cases where there is too much regenerative energy for
the available braking power.
To prevent the DC-link voltage from exceeding the threshold, the Vdc-max controller must be
enabled (p1240) and the device supply voltage set accordingly (p0210).
338
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3