Article number
Frame size
Weight
Recommended fuse
2)
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Minimum current required for reliable triggering of the protective devices.
3)
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
6SL3330– 1TG33–0AA3
FB
kg
96
3NE1230-2
1
315
2
kA
3
3)
5.2 Basic Line Modules
1TG34–3AA3
1TG36–8AA3
FB
FB
96
96
3NE1333-2
3NE1436-2
1
1
450
630
2
3
4.4
8
Line Modules
1TG41–1AA3
GB
214
3NE1334-2
2
500
3
10.4
153