Active Line Modules, 500 - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.4.6.2
Active Line Modules, 500 ... 690 V 3 AC
Table 5- 43
Technical data for Active Line Modules, 3 AC 500 V ... 690 V
Article number
Rated power
- For I
(50 Hz, 690 V)
n_DC
- For I
(50 Hz, 690 V)
H_DC
- For I
(50 Hz, 500 V)
n_DC
- For I
(50 Hz, 500 V)
H_DC
- For I
(60 Hz, 575 V)
n_DC
- For I
(60 Hz, 575 V)
H_DC
DC-link current
- Rated current I
n_DC
- Base load current I
H_DC
- Maximum current I
max_DC
Infeed/regenerative feedback current
- Rated current I
n_E
- Maximum current I
max_E
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- DC-link voltage
Pulse frequency
Current consumption
- Electronics current consumption (24 VDC)
- 500 VAC
- 690 VAC
Max. ambient temperature
- Without derating
- With derating
DC link capacitance
- Active Line Module
- Drive line-up, max.
Power loss
1)
- At 50 Hz 690 V
- At 60 Hz 575 V
Cooling air requirement
Sound pressure level
2)
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection PE1
- PE connection PE2
Max. cable length
3) 4)
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
6SL3330–
7TG35–8AA3
kW
630
kW
620
kW
447
kW
450
HP
675
HP
506
A
644
A
573
A
966
A
575
A
862
V
3AC 500 -10% (-15% < 1 min) ... 3AC 690 +10%
ACrms
Hz
V
DC
V
DC
kHz
2.5
A
1.4
A
3.0
A
2.1
° C
40
° C
55
µF
7400
µF
59200
kW
6.8
kW
6.2
m
/s
0.78
3
dB(A)
70 / 73
M12
mm²
4 x 240
mm²
Busbar
mm²
1 x 240
mm²
2 x 240
m
2250
m
3375
IP00
5.4 Active Line Modules
7TG37–4AA3
7TG41–0AA3
800
1100
705
980
560
780
510
710
900
1250
600
1000
823
1148
732
1022
1234
1722
735
1025
1102
1537
47 ... 63Hz
24 (20.4 ... 28.8)
1.5 x U
line
2.5
2.5
1.5
1.7
4.4
4.4
3.1
3.1
40
40
55
55
11100
14400
153600
153600
10.2
13.6
9.6
12.9
1.08
1.08
71 / 73
71 / 73
Flat connector for screw
M12
M12
6 x 240
6 x 240
Busbar
Busbar
1 x 240
1 x 240
3 x 240
3 x 240
2250
2250
3375
3375
IP00
IP00
Line Modules
7TG41–3AA3
1400
1215
965
880
1500
1250
1422
1266
2133
1270
1905
2.5
1.7
4.4
3.1
40
55
19200
153600
16.5
15.3
1.08
71 / 73
M12
6 x 240
Busbar
1 x 240
3 x 240
2250
3375
IP00
213

Advertisement

Table of Contents
loading

Table of Contents