Line/Load Connection; Drive-Cliq Interface X500 - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.7 Active Interface Modules Chassis-2
NOTICE
Damage to the device due to different phase sequence in the precharging and main
circuits
Different phase sequences in the pre-charging and main circuits can overload and destroy
the pre-charging resistors during the brief overlap period, where both contactors are
simultaneously closed.
• Connect the power cables to the precharging and main circuits with the same phase
4.7.3.3

Line/load connection

Table 4- 32
Connections for Active Interface Modules Chassis-2
Terminals
X1: U1, V1, W1
X2: U2, V2, W2
PE connection
Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1)
4.7.3.4

DRIVE-CLiQ interface X500

Table 4- 33
Connector
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
108
sequence.
Designations
Voltage: 380 V 3 AC -10% (-15% < 1 min) ... 480 V 3 AC +10%
Frequency: 47 ... 63 Hz
Connection: 2 holes 13.5 x 20.5 mm (M12, 50 Nm) flat connector for busbar connection
The following cross-sections are recommended when using copper busbars to establish the
connection:
Frame size FS2: 80 mm x 6 mm
Frame size FS4: 80 mm x 8 mm
Frame size FS4+: 80 mm x 8 mm
Connecting thread: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
DRIVE-CLiQ interface X500
PIN
1
2
3
4
5
6
7
8
A
B
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3