Electrical Connection - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.5.6

Electrical connection

Attaching the PE connections
The 3 PE connections must be attached before installing the Active Line Module. The
connecting busbars are included in the accessory pack.
Secure each PE connection with 2 screws on the Active Line Module, torque 25 Nm.
Figure 5-51
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Attaching the PE connections
Line Modules
5.5 Active Line Modules Chassis-2
241