Note
Derating factors for pulse frequencies in the range between two fixed values
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.
Maximum output frequencies achieved by increasing the pulse frequency
The adjustable pulse frequencies - and therefore the output frequencies that can be achieved
with the factory-set current controller clock cycles - are listed below.
Table 6- 22
Maximum output frequencies achieved by increasing the pulse frequency
Current controller
clock cycle
T
I
250 µs
1)
400 µs
2)
As factory setting, the following devices have a current controller clock cycle of 250 µs - and a pulse frequency of 2 kHz:
1)
- 510 ... 720 V DC: ≤250 kW / 490 A, 6SL3320-1TE41-4AS3
As factory setting, the following devices have a current controller clock cycle of 400 µs - and a pulse frequency of
2)
1.25 kHz:
- 510 ... 720 V DC: ≥315 kW / 605 A, with the exception of 6SL3320-1TE41-4AS3
- 675 ... 1035 V DC: All power ratings
With the "High output frequencies" license, which can be ordered as option J01 on the CompactFlash card for SINAMICS
3)
S120, the maximum output frequency is increased up to 650 Hz.
Refer to the Low Voltage Configuration Manual for current controller clock cycles deviating
from the factory setting.
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Adjustable pulse
frequencies
V/f operating mode
f
p
2 kHz
4 kHz
8 kHz
1.25 kHz
2.50 kHz
5.00 kHz
7.50 kHz
Maximum achievable output frequency f
Vector operating
166 Hz
333 Hz
550 Hz
3)
104 Hz
208 Hz
416 Hz
550 Hz
3)
Motor Modules
6.1 Motor Modules Chassis
A
Servo mode
mode
166 Hz
333 Hz
333 Hz
550 Hz
480 Hz
550 Hz
104 Hz
208 Hz
300 Hz
300 Hz
3)
3)
-
-
-
-
289