Line Modules
5.4 Active Line Modules
Article number
DC link capacitance
- Active Line Module
- Drive line-up, max.
Power loss
1)
- At 50 Hz 400 V
- At 60 Hz 460 V
Cooling air requirement
Sound pressure level
2)
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection PE1
- PE connection PE2
Max. cable length
3) 4)
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse
5)
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
Total sound pressure level of Active Interface Module and Active Line Module.
2)
The cable lengths are valid for use in the IT system. When used in the TN system, the cable lengths are shortened to 30%
3)
of the specified value.
When used in the TN system and when operating the connected Motor Modules with increased pulse frequency, you will
4)
receive the permitted cable lengths upon request.
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
5)
Minimum current required for reliable triggering of the protective devices.
6)
208
6SL3330– 7TE32–1AA3
µF
µF
kW
kW
m
/s
3
dB(A)
mm²
mm²
mm²
mm²
m
m
mm
mm
mm
kg
kA
6)
7TE32–6AA3
4200
5200
41600
41600
2.2
2.7
2.3
2.9
0.17
0.23
64 / 67
71 / 71
Flat connector for screw
M10
M10
2 x 185
2 x 185
2 x 185
2 x 185
2 x 185
2 x 185
2 x 185
2 x 185
2700
2700
4050
4050
IP20
IP20
326
326
1400
1400
356
356
FX
FX
95
95
3NE1230-2
3NE1331-2
1
1
315
350
2
2
6.2
10.5
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
7TE33–8AA3
7TE35–0AA3
7800
9600
76800
76800
3.9
4.8
4.2
5.1
0.36
0.36
69 / 73
69 / 73
M10
M10
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2700
2700
4050
4050
IP20
IP20
326
326
1533
1533
545
545
GX
GX
136
136
3NE1334-2
3NE1436-2
1
1
500
630
3
3
10.5
8
Air-cooled chassis power units