Dc Link Components; Braking Module; Description - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

DC link components

7.1

Braking Module

7.1.1

Description

A Braking Module and an external braking resistor are required to bring drives to a controlled
standstill in the event of a power failure (e.g. emergency retraction or EMERGENCY STOP
category 1) or limit the DC-link voltage if the generator is operated for a short period of time,
for example because there is no regenerative feedback capability into the supply network
when a Basic Line Module is used. The Braking Module contains the power electronics and
the associated control.
During operation the DC-link energy is converted into heat loss in an external braking resistor
outside of the control cabinet. Braking Modules function autonomously. Parallel operation of
several braking modules is possible. In this case, each Braking Module must have its own
braking resistor.
Up to 3 slots are available depending on the size of the Line Module or Motor Module:
Frame sizes FB, GB, GD, FX, GX:
Frame size HX:
Frame size JX:
Frame size FS2, FS4:
Note
No installation in Motor Modules Chassis-2
It is not permissible to install the Braking Modules in a Motor Module Chassis-2.
Figure 7-1
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Braking Module
1 mounting location
2 mounting locations
3 mounting locations
Installation not possible
7