Line/Load Connection - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
5.3 Smart Line Modules
NOTICE
Damage to the device due to different phase sequence in the precharging and main
circuits
If the precharging and main circuits have different phase sequences, the precharging
resistors could be overloaded and destroyed during the brief overlap period where both
contactors are simultaneously closed.
• Wire the precharging and main circuits with the same phase sequence.
5.3.3.3

Line/load connection

Table 5- 18
Line/load connection of the Smart Line Module
Terminals
Technical specifications
U1, V1, W1
Voltage:
3 AC power input
Frequency: 47 ... 63 Hz
Connecting thread:
DCPA, DCNA
Voltage:
Connection for
Braking Module
Connections:
DCP, DCN
Voltage:
DC power output
Connections:
PE connection
Connecting thread:
PE1, PE2
Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1)
166
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
500 ... 630 V DC
650 ... 900 V DC
Frame size GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HX / JX: Connection for connection clip
500 ... 630 V DC
650 ... 900 V DC
Frame size GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: d = 12 mm (M12/50 Nm) flat connector for busbar
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
1)
1)
1)
1)
1)