Set Communication - ADF Web HD67056-B2-20 User Manual

M-bus master/ bacnet slave - converter
Table of Contents

Advertisement

Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two buses, BACnet and M-Bus.
By Pressing the
"Set
Communication" button from the main window for SW67056 (Fig. 2) the window
"Set Communication" appears (Fig. 3).
The window is divided in three sections, one for selecting the type of BACnet (in relation to the device
used), one for the BACnet parameters and the other for the M-Bus parameters.
In the section "BACnet Type" is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
If selected "BACnet/IP" the means of the fields for "BACnet" are:
In the fields
"IP
ADDRESS" the IP address of BACnet/IP side of the converter is defined;
In the fields
"SUBNET
In the fields "GATEWAY" the default gateway of the network is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field "Port" the port used for BACnet communication is defined. The default port used for
BACnet communication is 47808, but is possible to insert any value (except 10000 and 10001);
In the field
"BACnet Device
In the field
"Device
Identifier" the ID of BACnet/IP side of the converter is defined;
If the field
"BACnet description up to 32
Objects can be up to 32 chars long.
The means of the fields for M-Bus are:
In the field "Baudrate" the baudrate of the M-Bus line is defined;
In the field "Parity" the parity of the M-Bus line is defined;
If the field
"Cyclic
Delay" the delay (expressed in seconds) between two M-Bus scanning is
defined;
In the field
"Node State value when slave device is not
value to assign to the "Node State" when the Gateway doesn't find the interrogated M-Bus slave.
ADFweb.com S.r.l.
Mask" the SubNet Mask of BACnet/IP side of the converter is defined;
Name" the name of BACnet/IP side of the converter is defined;
chars" is checked, the description for the BACnet
User Manual M-Bus Master / BACnet Slave
Document code: MN67056_ENG
present" it is possible to insert the
Revision 1.200
Page 17 of 39
Figure 3a: "Set
Communication" window