M-Bus Master/ BACnet Slave - Converter
(Order Codes:
HD67056-B2-20, HD67056-B2-40,
HD67056-B2-80, HD67056-B2-160,
HD67056-B2-250)
(Order Codes:
HD67056-MSTP-20, HD67056-MSTP-40,
HD67056- MSTP-80, HD67056-MSTP-160,
HD67056- MSTP-250)
For Website information:
www.adfweb.com?Product=HD67056-B2
For Price information:
www.adfweb.com?Price=HD67056-B2-20
www.adfweb.com?Price=HD67056-B2-40
www.adfweb.com?Price=HD67056-B2-80
www.adfweb.com?Price=HD67056-B2-160
www.adfweb.com?Price=HD67056-B2-250
Benefits and Main Features:
Very easy to configure
Up to 250 standard M-Bus devices connected to the Converter
Power Supply 15...21V AC or 18...35V DC
Temperature range: -40°C/+85°C (-40°F/+185°F)
User Manual
ADFweb.com S.r.l.
User Manual M-Bus Master / BACnet Slave
Document code: MN67056_ENG
Revision 1.200
For others M-Bus products see also the following link:
Converter - M-Bus /
www.adfweb.com?Product=HD67021
www.adfweb.com?Product=HD67022
Analyzer / Scanner /Sniffer M-Bus
www.adfweb.com?Product=HD67031
M-Bus – Repeater - Isolator
www.adfweb.com?Product=HD67032M
Converter - M-Bus / Modbus Slave
www.adfweb.com?Product=HD67029M-232
www.adfweb.com?Product=HD67029M-485
Gateway M-Bus / Modbus TCP
www.adfweb.com?Product=HD67044
Gateway M-Bus / CANopen
www.adfweb.com?Product=HD67051-B2
Gateway M-Bus / PROFIBUS
www.adfweb.com?Product=HD67053M
Gateway M-Bus Concentrator
www.adfweb.com?Product=HD67054M
Gateway M-Bus Slave / Modbus RTU master
www.adfweb.com?Product=HD67059M-232
Do you have an your customer protocol?
www.adfweb.com?Product=HD67003
Do you need to choose a device? do you want help?
www.adfweb.com?Cmd=helpme
Page 1 of 39
(RS232)
(RS485)
(on RS232)
(on RS485)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HD67056-B2-20 and is the answer not in the manual?

Questions and answers

Summary of Contents for ADF Web HD67056-B2-20

  • Page 1 Page 1 of 39 Industrial Electronic Devices User Manual Revision 1.200 English M-Bus Master/ BACnet Slave - Converter (Order Codes: HD67056-B2-20, HD67056-B2-40, HD67056-B2-80, HD67056-B2-160, HD67056-B2-250) (Order Codes: HD67056-MSTP-20, HD67056-MSTP-40, For others M-Bus products see also the following link: HD67056- MSTP-80, HD67056-MSTP-160,...
  • Page 2: Table Of Contents

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 2 of 39 Industrial Electronic Devices INDEX: UPDATED DOCUMENTATION: Dear customer, we thank you for your attention and we remind you that Page you need to check that the following document is: INDEX UPDATED DOCUMENTATION Updated...
  • Page 3: Security Alert

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 3 of 39 Industrial Electronic Devices SECURITY ALERT: ENERAL NFORMATION To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and safety regulation are required for each individual application.
  • Page 4: Example Of Connection

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 4 of 39 Industrial Electronic Devices EXAMPLE OF CONNECTION: ADFweb.com S.r.l.
  • Page 5: Connection Scheme

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 5 of 39 Industrial Electronic Devices CONNECTION SCHEME: Figure 1a: Connection scheme for HD67056-B2-xxx ADFweb.com S.r.l.
  • Page 6 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 6 of 39 Industrial Electronic Devices Figure 1b: Connection scheme for HD67056-MSTP-xxx ADFweb.com S.r.l.
  • Page 7: Characteristics

    At the Converter can be connected up to 250 standard M-Bus devices. This number depends of the code expressed by the xxx number: HD67056-B2-20 and HD67056-MSTP-20 support up to 20 M-Bus devices; HD67056-B2-40 and HD67056-MSTP-40 support up to 40 M-Bus devices;...
  • Page 8: Power Supply

    Vmax Consumption at 24V DC: Device No Load [W/VA] Full Load [W/VA]* HD67056-B2-20, HD67056-MSTP-20 HD67056-B2-40, HD67056-MSTP-40 HD67056-B2-80, HD67056-MSTP-80 HD67056-B2-160, HD67056-MSTP-160 HD67056-B2-250, HD67056-MSTP-250 * This value is with all the Slave M-Bus devices of the code (20, 40, 80, 160, 250) connected to the line...
  • Page 9: Function Modes

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 9 of 39 Industrial Electronic Devices FUNCTION MODES: The device has got two functions mode depending of the position of the ‘Dip1 of Dip-Switch A’: The first, with ‘Dip1 of Dip-Switch A’ at “OFF” position, is used for the normal working of the device. The second, with ‘Dip1 of Dip-Switch A’...
  • Page 10: Leds

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 10 of 39 Industrial Electronic Devices LEDS: The device has got five LEDs that are used to give information of the functioning status. The various meanings of the LEDs are described in the table below. Normal Mode Boot Mode Blinks quickly: Boot state...
  • Page 11: Bacnet/Ip (Hd67056-B2-Xxx Serie)

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 11 of 39 Industrial Electronic Devices BACNET/IP (HD67056-B2-XXX SERIE): BACnet/IP connection must be made using Connector3 of HD67056-B2 with at least a Category 5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps.
  • Page 12: M-Bus

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 12 of 39 Industrial Electronic Devices M-BUS: The M-Bus is a unpolarized bus. A two wire standard telephone cable (JYStY N*2*0.8 mm) is used as the transmission medium for the M-Bus. The maximum distance between a slave and the repeater is 350m;...
  • Page 13: Use Of Compositor Sw67056

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 13 of 39 Industrial Electronic Devices USE OF COMPOSITOR SW67056: To configure the Converter, use the available software that runs with Windows called SW67056. It is downloadable on the site www.adfweb.com and its operation is described in this document.
  • Page 14: New Project / Open Project

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 14 of 39 Industrial Electronic Devices NEW CONFIGURATION / OPEN CONFIGURATION: “New Configuration” button creates the folder which contains the entire device’s configuration. A device’s configuration can also be imported or exported: To clone the configurations of a Programmable “M-Bus Master / BACnet Slave - Converter”...
  • Page 15: Software Options

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 15 of 39 Industrial Electronic Devices SOFTWARE OPTIONS: By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the compositor.
  • Page 16 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 16 of 39 Industrial Electronic Devices In the section “Software Settings”, it is possible to enable/disable some keyboard’s commands for an easier navigation inside the tables contained in the different sections of the software.
  • Page 17: Set Communication

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 17 of 39 Industrial Electronic Devices SET COMMUNICATION: This section define the fundamental communication parameters of two buses, BACnet and M-Bus. By Pressing the “Set Communication” button from the main window for SW67056 (Fig. 2) the window “Set Communication”...
  • Page 18 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 18 of 39 Industrial Electronic Devices If selected “BACnet MS/TP”, the means of the fields for “BACnet” are: In the field “Baudrate” the data rate of the BACnet line is defined; In the field “Parity”...
  • Page 19: M-Bus

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 19 of 39 Industrial Electronic Devices M-BUS By Pressing the “M-Bus” button from the main window for SW67056 (Fig. 2) the window “M-Bus Network” appears (Fig. 4). In the section “Nodes”...
  • Page 20 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 20 of 39 Industrial Electronic Devices In the field “Send Reset App.” is checked, the converter sends the “Application Reset” command to the slave. In the field “Variables List”...
  • Page 21 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 21 of 39 Industrial Electronic Devices ECTION ARIABLES Selecting the desired node it is possible to add a variable. In order to create a new variable it is necessary to fill these items: To use the created variable the field “Enable Variable”...
  • Page 22 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 22 of 39 Industrial Electronic Devices If the field “From BCD to Integer” is checked the converter converts the BCD value of variable in Integer format. This happens only if the variable is in BCD format;...
  • Page 23 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 23 of 39 Industrial Electronic Devices SECTION VARIABLES (BY POSITION): Selecting the desired node it is possible to add a variable. In order to create a new variable it is necessary to fill these items: To use the created variable the field “Enable Variable”...
  • Page 24 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 24 of 39 Industrial Electronic Devices Example: 0x68 – Start Byte 0xBD – L Fied 0xBD – L Field 0x68 – Start Byte 0x08 – C Field 0x02 –...
  • Page 25 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 25 of 39 Industrial Electronic Devices ASTE AND ELETE TEMS By pressing the right button of the mouse over an item (Variable or Node) it is possible to Copy, Paste and Delete. It is possible to Copy a variable from a Node and copy it to another Node, or copy a Variable from a project and paste in another one.
  • Page 26 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 26 of 39 Industrial Electronic Devices BACNET ENG. UNIT: By pressing to button the left window appears (Fig. 5). Is possible to insert directly the Unit (using its unique number) by compiling the “Selected BACnet Engineering Unit”...
  • Page 27 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 27 of 39 Industrial Electronic Devices Possible choices for the fields used to create a variable: Type of Data: Function Field: |_Energy (Wh) [BACnet Data Type: 1] |_Instantaneous Value |_Energy (J) |_Minimum Value...
  • Page 28 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 28 of 39 Industrial Electronic Devices VIFE: |_ Not Selected |_ Period of tariff months(s) |_ Credit of the nominal local legal currency units |_ Period of tariff year(s) |_ Debit of the nominal local legal currency units |_ dimensionless/ no VIF |_ Access Number (transmission count)
  • Page 29 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 29 of 39 Industrial Electronic Devices |_ per second |_ # of exceeds of lower/upper limit |_ per minute |_ Date(/time) of begin/end of first/last lower/upper limit exceed[2] |_ per hour |_ Duration of limit exceed...
  • Page 30: Bacnet Ede File

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 30 of 39 Industrial Electronic Devices BACNET EDE FILE: By Pressing the “BACNET EDE FILE” button from the main window for SW67056 (Fig. 2) it is possible to generate the EDE file to be imported into the BACnet Master.
  • Page 31 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 31 of 39 Industrial Electronic Devices Swap Identification: This field is used for select the Swap mode of Identification Number. At the moment there are these possibilities: None;...
  • Page 32: Update Device

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 32 of 39 Industrial Electronic Devices UPDATE DEVICE: By pressing the “Update Device” button, it is possible to load the created Configuration into the device; and also the Firmware, if necessary. This by using the Ethernet port. If you don’t know the actual IP address of the device you have to use this procedure: Turn OFF the Device;...
  • Page 33 User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 33 of 39 Industrial Electronic Devices Note: When you receive the device, for the first time, you also have to update the Firmware in the HD67056 device. Warning: If Fig.
  • Page 34: Scan & Decode Function

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 34 of 39 Industrial Electronic Devices SCAN & DECODE FUNCTION: “SCAN & DECODE” functions are integrated in the configurator software SW67056. It is possible to access to these functions by simple click on the “...
  • Page 35: Mechanical Dimensions

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 35 of 39 Industrial Electronic Devices MECHANICAL DIMENSIONS: Figure 8: Mechanical dimensions scheme for HD67056 ADFweb.com S.r.l.
  • Page 36: Ordering Informations

    B: Modulbox 4M, 35mm DIN Rail mounting Device Family HD67056: M-Bus Master / BACnet - Converter Order Code: HD67056-B2-20 Converter M-Bus Master / BACnet/IP Slave (up to 20 slaves connected to M-Bus) Order Code: HD67056-B2-40 Converter M-Bus Master / BACnet/IP Slave (up to 40 slaves connected to M-Bus)
  • Page 37: Accessories

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 37 of 39 Industrial Electronic Devices ACCESSORIES: Order Code: APW020 Power Supply for M-Bus Master device that supports up to 20 Slaves Order Code: APW040 Power Supply for M-Bus Master device that supports up to 40 Slaves Order Code: APW080 Power Supply for M-Bus Master device that supports up to 80 Slaves...
  • Page 38: Disclaimer

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 38 of 39 Industrial Electronic Devices DISCLAIMER: All technical content within this document can be modified without notice. The content of the document is a under continual renewal. For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal conditions repairs are charged to the user.
  • Page 39: Warranties And Technical Support

    User Manual M-Bus Master / BACnet Slave Document code: MN67056_ENG Revision 1.200 Page 39 of 39 Industrial Electronic Devices WARRANTIES AND TECHNICAL SUPPORT: For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com. Otherwise contact us at the address support@adfweb.com RETURN POLICY: If while using your product you have any problem and you wish to exchange or repair it, please do the following:...

Table of Contents

Save PDF