Parameter Setting - Siemens SED2 Commissioning Manual

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

8.1.1 Parameter setting

Start with quick commissioning according to application 1
Par. no.
Value
Parameter function
P0003
3
User access level
P2182
14 Hz
Belt threshold 1
Par. no.
Value
Parameter function
P2183
30 Hz
Belt threshold 2
P2184
51 Hz
Belt threshold 3
r0031
15 Hz
Adjust with the
r0031
30 Hz
Adjust with the
r0031
50 Hz
Adjust with the
P2185
≥+ 25%
Upper torque threshold
frequency 1
P2186
≥- 25%
Lower torque threshold
frequency 1
P2187
≥+ 25%
Upper torque threshold
frequency 2
P2188
≥- 25%
Lower torque threshold
frequency 2
P2189
≥+ 25%
Upper torque threshold
frequency 3
P2190
≥- 25%
Lower torque threshold
frequency 3
P2192
Suggest
Time delay for belt failure
30 s
P2181
6
Belt failure detection mode Trip on high / low torque / speed
54 / 100
Siemens
Building Technologies
Function selection
Expert access
Sets a frequency threshold F1 for comparing actual torque to
torque the envelope for belt failure detection. The frequency
torque envelope is defined by 9 parameters – 3 are frequency
parameters (P2182 - P2184) and the other 6 define the low
and high torque limits (P2185 - P2190) for each frequency
Function selection
Sets a threshold F2 for comparing actual torque to torque
within the envelope for belt failure detection
Sets a threshold F3 for comparing actual torque to torque
within the envelope for belt failure detection
button
Read the torque at 15 Hz and note it here: ......................
button
Read the torque at 30 Hz and note it here: ......................
button
Read the torque at 45 Hz and note it here: ......................
Add 25% to the torque reading taken at 15 Hz
Subtract 25% of the torque reading taken at 15 Hz
Add 25% to the torque reading taken at 30 Hz
Subtract 25% of the torque reading taken at 30 Hz
Add 25% to the torque reading taken at 50 Hz
Subtract 25% of the torque reading taken at 50 Hz
Defines a delay before warning / trip becomes active. It is
used to eliminate events caused by transient conditions. It is
used for both methods of fault detection
Commissioning Guide
8 Additional functions
CM1G5192en
29.07.2010